• 0.9 output power factor
• 0.99 input power factor
• Three phase input model support three phase PFC
• Input THDI < 5%
• Output voltage regulation 1%
• Output frequency regulation 0.1%
• The efficiency up to 94%
• Efficiency up to 93.5% when take the 30% load
• ECO mode efficiency up to 98%
• Battery voltage can be choice depend on capacity
• Convenience to get more back up time
• Convenience to save cost of battery
• Intelligent battery monitors
• Standant charge current 4A
• Adjustable charge current
• Optional 8A charger
• Support maximum 3 units for parallel working
• Support three phase input or single phase input for three phase UPS
• Super wide input voltage and frequency range suitable for bad power electirc environment
• Digital control DSP technology and best power component make the system safe and reliable
MODEL |
NEOLINE 3L 210 |
|||
Rated Power |
10KVA/9KW |
|||
Rated Voltage |
220VAC/380VAC 3phase with ground |
|||
Power factor |
≥ 0.95 (Three phase) |
|||
Rated Frequency |
40-70 Hz (50/60 Auto-sense) |
|||
OUTPUT |
||||
Voltage Regulation |
208/220/230/240VAC (±1%) |
|||
Power Factor |
0.9 |
|||
Voltage Distortion |
Linear load < 2% Non-linear load < 5% |
|||
Frequency Regulation |
50/60 Hz±0.5Hz |
|||
Current Crest Ratio |
3:1 |
|||
Overload capability |
105%~125% for 10 min;125%~150% for 30 s; >150% for 500 ms |
|||
Transfer Time |
0ms (AC mode→Battery mode) |
|||
Efficiency |
> >94% |
|||
BATTERY |
||||
DC voltage |
192VDC |
|||
Recharge Current |
4A |
|||
DISPLAY |
||||
LCD |
Display input/output Voltage, Frequency, Battery voltage, Battery capacity, Loading rate. |
|||
COMMUNICATION |
||||
Interface |
Smart RS232, SNMP(Optional),USB (Optional) |
|||
PHYSICS CHARACTERISTIC |
||||
Dimensions (mm) HxWxD |
500x212x420 |
|||
Net weight (kg) |
16.9 |
|||
ENVIRONMENT |
||||
Operating temperature range |
0°C ~ 40 °C |
|||
Audible Noise |
< 55 dBA |